The Problem

KNX systems were designed to integrate any kind of installation, from small to a very large ones. The traditional KNX TP (Twisted Pair) topology was supposed to support up to 15 areas with 15 complete lines each, but in practice, when such big installations have to be monitored from one or more central points, KNX TP main and backbone lines cannot cope with tens or even hundreds of accumulated line traffic.

KNX IP routers were created about 12 years ago to deal with this situation, but they are not enough when we have several lines in a KNX system. If we want to monitor a big KNX system using visualisation/control software, we could use the KNXnet/IP routing connection (Falcon) to do so. Whilst the KNXnet/IP (tunnelling) connection is robust (like a USB connection), it only allows us to see one line´s traffic, so this connection is not enough for visualising the entire system. Using KNXnet/IP routing means that every telegram has to be redirected to the backbone using dummies or, better still, editing filter tables manually.

By using an IP backbone, we have solved the bandwidth issue that we had with TP systems, but this is not the only problem we have in large installations. For example, imagine that we have a system with 100 KNX (IP) lines. For the IP-Routers, acting as line couplers, the traffic is only x1 on the local side, but it will be x100 on the main side. This will result in a bottleneck on each coupler at the main line, and many of the telegrams could be lost.

The Solution

It is clear that the best IP connection is KNXnet/IP (tunnelling), but we only have one possible connection using the Falcon driver. On other hand, using KNXnet/IP routing, we have to launch all of the traffic to the backbone, so we may suffer with the line couplers.

The solution is not complicated to understand: extra help, in the form of software, is needed to avoid this traffic in the backbone by establishing simultaneous IP tunnelling connections, one for each line. So, we will have all of the project data in an item tree (group address (GA), but also physical address (PA)), mapped for each line. The NETxAutomation OPC Server and BMS Server can do this easily – indeed NETxAutomation is the OPC server recommended since 2006 by KNX International for large KNX installations. In the following example, we will use NETxAutomation´s BMS Server, because we will use this tool for other, future examples too.

Establishing Simultaneous IP Tunnelling Connections

First, we need to get all of the project data from ETS5. Normally, this would take a lot of time and effort because we need to know which GA or PA is related to which line (IP tunnelling address). However, we will use a free ETS app, the NETx BMS App, which allow us to do this in seconds.

After installing the app, simply select the NETx BMS App from ETS5 Extras Menu (also available in ETS4).

Step 1 - Select the free NETx BMS App to extract all data from the ETS5 project.
Step 1 – Select the free NETx BMS App to extract all data from the ETS5 project.

Then select the options you wish to export. Do not worry if the IP tunnelling addresses are not parameterised, the app will ask for that.

Step 2 - Export all of the data needed from the ETS5 project.
Step 2 – Export all of the data needed from the ETS5 project.

After exporting, we can now do the import process in the NETxAutomation BMS Server Studio (you can download a free 30-day trial from www.netxautomation.com). Just select the KNX menu and the first option, as shown below.

Step 3 - Select NETx App file to Import KNX project data into the BMS Server Studio.
Step 3 – Select NETx App file to Import KNX project data into the BMS Server Studio.

The import process will take also only a few seconds.

Step 4 - Importation process of KNX project data into the BMS Server Studio.
Step 4 – Importation process of KNX project data into the BMS Server Studio.
The importation process is finished in seconds.
The importation process is finished in seconds.

After restarting the BMS Server, we can see all of the KNX project data (GAs and also PAs if needed) mapped for each line (represented by their respective IP tunnelling addresses).

Final result: all of the data of the ETS project is in the BMS Server Item tree.
Final result: all of the data of the ETS project is in the BMS Server Item tree.

The result is that we can now use this Item tree for visualization/control in any OPC client for example, and we do not need all of the traffic in the backbone. This really is the proper way to manage a large KNX Project.

Another example of using this method for a large KNX project could be the integration of multiple stores, such as, say, 200 small supermarkets. If we were to have a VPN between all of them, we could manage all of these stores with just one OPC server or BMS server. This could be a much cheaper solution, because all we would need are IP interfaces to do this – no IP routing multicast would be needed at all.

Conclusion

When we have to manage a large KNX installation, the data traffic can be a nightmare if we need to monitor the entire system, even if we use IP routers. To avoid the bottleneck issue in IP routers, extra software is required. The NETxAutomation BMS Server includes a KNX OPC server and many other functions, and was the tool used in this example. Furthermore, with the free NETx BMS App, we can export all of the mapped data of any KNX project to the NETxAutomation´s OPC server and the BMS server, easily and quickly.

Julio Díaz García is the Owner of Sapienx Automation. He is an Engineer and KNX International Award-winning KNX++ Tutor. Sapienx Automation provides engineering, training and consultancy services for smart buildings, smart metering and smart cities.

www.sapienx.es

Share on facebook
Share
Share on twitter
Tweet
Share on linkedin
Share

SPONSORS

Interra iX3 4” Touch Panel


Interra iX3 4” Touch Panel
A next-generation room controller that transforms environmental management. With integrated sensors for temperature, humidity, brightness, and air quality (optional ...

Intesis DALI to KNX PRO


Intesis DALI to KNX PRO
The new Intesis DALI-2 to KNX TP PRO Gateway is a multi-master application controller for DALI-2 ballast ...

Clever solution for existing KNX properties


Clever solution for existing KNX properties
Anyone who built their home over three decades ago with the European installation bus can now upgrade it with modern ...

Interra KNX AC Gateway


Interra KNX AC Gateway
Interra KNX AC Gateway: Smart Climate Control Solutions The Interra KNX AC Gateway offers an innovative solution for climate control ...